Loading...
1981-055• _ ORDINANCE NO. 81- 55 AN ORDINANCE AMENDING TITLE 15.OF THE VILLAGE OF BUFFALO GROVE MUNICIPAL CODE WHEREAS, the Village of Buffalo Grove is a Home Rule Unit by virtue of the provisions of the Constitution of the State of Illinois of 1970. NOW, THEREFORE, BE IT ORDAINED BY THE VILLAGE PRESIDENT AND BOARD OF TRUSTEES OF THE VILLAGE OF BUFFALO GROVE, COOK AND LAKE COUNTIES, ILLINOIS: SECTION 1 Chapter 15.08 of the Village of Buffalo Grove Municipal Code is hereby amended to read as follows: Chapter 15:08:010 Adopted by reference. The 1981 National Electrical Code as modified in this chapter is hereby adopted by reference. In the event any of the provisions of the 1981 National Electrical Code are. i 'n conflict with any ordinances of the village or with the state law, the most restrictive provision among them shall prevail. Chapter 15;08.020 Filing. Three copies of the 1981 National Electrical Code shall be kept on file in the office of the village clerk for public use, Uspection and examination. Chapter 15:08:030 Amendments. The 1981 National Electrical Code is hereby amended as follows: Article 110 -23. Identificati::on of Electrical Contractors. The name of the electrical contractor performing the work shall be displayed on the service panel box. Article 210 -24. Branch - Circuit Requirements!- Summary. The requirements for circuits having two or more outlets, other than the receptacle circuits of Section 220 -3.(b) as specifically pro- vided for above, are summarized in Table 210 -24. Detached garages shall be on a separate circuit and shall Include the following: (a) A ceiling light controlled by a wall switch. (b) A minimum of one (1) ground fault circuit - interrupter receptacle. Article 210 -52. 1. Dwelling Unit Receptacle Outlets. (a) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sun room, bedroom, recreation room, foyer, or similar rooms of dwelling units, receptacle outlets shall be installed so that no point along the floor line in any wall space is more than 6 feet (1.83 m), measured horizontally, from an outlet in that space, including any wall space 2 feet (610 mm) or more in width and the wall space occupied by sliding panels in exterior walls. The wall space afforded by fixed room dividers, such as free- standing bar -type counters, shall be included in the 6 -foot (1.83 -m) measurement. As used in this section a "wall space" shall be considered a wall unbroken along the floor line by doorways, fireplaces, and similar openings.. Each wall space 2 or more feet (610 mm or more.) wide shall be treated individually and separately from other wall spaces within the room. A wall space shall be permitted to include two or more walls of a room (around corners) where unbroken at the floor line. qW -2- A duplex wall receptacle shall be installed in each hallway. Receptacle outlets shall, insofar as practicable, be spaced equal distances apart. Receptacle outlets in floors shall not be counted as part of the required number of receptacle outlets unless located close to the wall. The receptacle outlets required by this section shall be in addition to any receptacle that is part of any lighting fixture of applicance, located within cabinets or cupboards, or located over 51-, feet (1.68 m) above the floor. Exception: Permanently installed electric baseboard heaters equipped with factory - installed receptacle outlets or outlets provided as a separate assembly by the manufacturer shall be permitted as the required outlet or outlets for the wall space utilized by such permanently installed heaters. Such receptacle outlets-shall not be connected to the heater circuits. Article 210 -70. Lighting Outlets Required. Lighting outlets shall be installed where specified in a and b) below. (a) Dwelling Unit(s). At least one wall switch - controlled lighting outlet shall be installed in every habitable room, in bathrooms, hallways, stairways, and attached garages; and at outdoor entrances. Where the preceding are accessible by more than one entry or exit, they shall have a light or lights controlled by a switch at each entry or exit.. (A vehicle door in an attached garage is not considered an outdoor entrance.) At least one lighting outlet shall be installed in an attic, underfloor space, utility room and basement. Exception No. 1: In habitable rooms, other than kitchens, one or more receptacles controlled by a wall switch shall be permitted in lieu of lighting outlets. Exception No. 2: In hallways, stairways, and at outdoor entrances-remote, central, or automatic control of lighting shall be permitted, Article 225 -10. Wiring on Buildings The installation of outside wi. ring on surfaces of buildings shall be permitted for circuits of not over'600 volts, nominal, in rigid metal conduit, in intermediate metal conduit, in rigid nonmetallic conduit as provided in Section.347 -2, in busways as provided in Article 364, or in electrical metallic tubing. Circuits of over 600 volts, nominal, shall be installed as provided for services in Section 230 -202. Circuits for sign and outline lighting shall be installed in accordance. with. Article 600. Article 230 -43. Wiring Methods for 600 Volts, Nominal, or Less. Service- entrance conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and limited to the following methods: (1) rigid metal conduit; (2) intermediate metal conduit; (3) elec- trical metallic tubing; (4) service- entrance cables; (5) wireways; (6) busways; (7) auxi::liary gutters; (8) rigid nonmetallic conduit; (9) caablebus; or (10) mineral- insulated, metal - sheathed cable. Approved cable tray systems shall be permitted to support cables approved for use as service- entrance conductors. See Arti:cl e.. 318. v -3- Article 230 -70. General. Means shall be provided to dis- connect all conductors in a building or other structure from the service- entrance conductors. Each service disconnecting means shall be permanently marked to identify it as a service disconnecting means and shall be of the type that is suitable for use as service equipment. Each service disconnecting means shall be suitable for the prevailing conditions. Service equipment installed in hazardous (classified) locations shall comply with the requirements of Articles 500 through 517. A main service disconnect shall be installed for every metered service. Article 230 -79. Rating of Disconnect. The service dis- connecting means shall have a rating not less than the load to be carried, determined in accordance with Article 220. In no case shall the rating be lower than specified in (a), (b), (c), (d), or (e) below. (a) One - Circuit Installation. For installations to supply on ly limtted Toads of a single branch circuit, the service disconnecting means shall have a rating of not less than 15 amperes. (b) Two- Circuit Installations. For installations consist- ing of not more than two 2 -wire branch circuits, the service disconnecting means shall have a rating of not less than 30 amperes. (c) One - Family Dwelling. For a one - family dwelling, the service disconnecting means shall have a rating of not less than 100 amperes, 3 -wire under either of the following conditions: (1) where the initial computed load is 10 kW or more, or (2) where the initial installation consists of six or more 2 -wire branch circuits. (d) Commercial and'Industrial Buildings. In commercial and industrial buildings, the minimum service shall be two - hundred (200) amperes. (.e) All Others. For all other installations the service disconnecting means shall have a rating of not less than 60 amperes. Article 230 -202. Service - Entrance Conductors. Service - entrance conductors to buildings or enclosures shall be installed to conform to the following: (a) Conductor'Size. Service conductors shall be not smaller than No. 6 unless in cable. Conductors in cable shall not -be smaller -than No. 8. (b) Wiring Methods. Service - entrance conductors shall be installed by means of one of the following wiring methods: (1) in rigid metal conduit; (2) in intermediate metal conduit; (3) in rigid nonmetallic conduit where encased in not less than 2 inches (50..8 mm) of concrete; (4) as multiconductor cable identified as service cable; (5) in cablebus; or (6) in busways. Underground service - entrance conductors shall conform to Section 710 -3(b). Cable tray systems shall be permitted to support cables identified as service- entrance conductors. See Article 318. (See Section 310 -6 for shielding of solid dielectric insulated conductors.) Article 250 -91. Material (:d) Prohibition of'Use of Aluminum Wire. The use of aluminum wire in ground or below grade for the purpose of grounding Is prohibi :ted, AU W - 4 - W Article 300-1. Scope. (c) Wiring for all circuits (except lighting circuits) in commercial and industrial buildings shall be 12 AWG rated conductors or larger. Article 310 -5. Minimum Size of Conductors. Whether solid or stranded, conductors shall not be smaller than No. 14 copper or No. 6 aluminum or copper -clad aluminum. Exception No. 1: For flexible cords as permitted by Section 400 -12. Exception No. 2: For fixture wire as permitted by Section 410 -23. Exception No. 3: For fractional hp motors as permitted by Section 430 -22 -. Exception No. 4 For cranes and hoists as permitted by Section 610 -14. Exception No. 5: For elevator control and signaling circuits as permitted by Section 620 -12. Exception No. 6: For Class 1, Class 2 and Class 3 circuits as permitted by Sections 725 -16, 725 -37, and 725 -40. Exception No. 7: For fire protective signaling circuits as permitted by Sections 760 -16, 760 -27, and 760 -30. Article 320 - Open Wiring on Insulators. Not enacted by reference. Article 324' -- Concealed Knob- and -Tube Wiring. Not enacted by reference. Article. 328 -4. Uses Permitted. (a) Branch Ci:rcui.ts. Use of FCC systems shall be permitted both far general purpose and appliance branch circuits, and for individual branch circuits. (b) Floors. Use of FCC systems shall be permitted on hard, sound, smooth, continuous floor surfaces made of con - crete, ceramic, or composition flooring, wood, and similar materials, and shall be used only for reworking obsolete wiring systems in office, commercial and industrial interior faci;li:ti:es or upon written authorization of the building official as to the special circumstances making necessary such. permission. (c)' Walls. Use of FCC systems shall be permitted on wall surfaces in - surface metal raceways. (d) damp Locations. Use of FCC systems in damp locations shall be- permitted. (e) Heated `Floors. Materials used for floors heated in excess of 30o C 860F) shall be identified as suitable for use at these temperatures. Article 333, -6. Use. Except where otherwise specified else- where in thIs Code, and where not subject to physical damage, Type AC cable shall be permitted for branch circuits and feeders i:n both. exposed and concealed work. Type AC cable shall be permitted in dry locations; for under - plaster extensions as provided in Article 344; and embedded in plaster finish on brick or other masonry, except in damp or wet locations. It shall be permissible to run or fish this cable in the air voids of masonry block or tile walls; where such walls are exposed or subject to excessive moisture or dampness or are below grade line, Type ACL cable shall be used. This cable shall contain lead - covered conductors (Type ACL) if used where exposed to the weather or to continuous moisture; for underground runs in raceways and embedded in masonry, concrete, or fill in buildings in course of construction; or where exposed to oil, or other conditions having a deteriorating effect on the insulation. -5- Type AC cable shall not be used where prohibited elsewhere in this Code, including (1) in theaters and similar locations, except as provided in Article 518, Places of Assembly; (2) in motion picture studios; (3) in any hazardous (classified) location; (4) where exposed to corrosive fumes or vapors; (5) on cranes or hoists, except as provided in Section 610 -11, Exception No. 3; (6) in storage battery rooms; (7) in hoistways or on elevators, except as provided in Section 620 -21; or (8) in commercial garages where prohibited in Article 511. Type AC cable shall not be used in new construction in lengths of greater than six (6) feet. Exception: See Section 501 -4(b), Exception. Type ACL cable shall not be used for direct burial in the earth. Article 334 -4. Uses Not Permitted. Type MC cable shall not be used where exposed to destructive corrosive conditions, such as direct burial in the earth, in concrete, or where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids. Type MC cable shall not be used in new construction in lengths of greater than six (6) feet. Exception: Where the metallic sheath is suitable for the conditions or is protected by material suitable for the conditions. Article 336 -3. Uses Permitted or Not Permitted. Not enacted by reference. Article 349 -3. Uses Permitted. Flexible metallic tubing shall be permitted to be used: (1) In dry locations, (2) in accessible locations when protected from physical damage or concealed, (3) Far 1000 volts maximum, (4) In branch circuits, (5) I'n final connections- to lighting fixtures and equipment, and (6) For remodeling work and in confined spaces. Article 349 -4. Uses'Not Permitted. Flexible metallic.tubing shall not be used (1) In hoi,stways, (2) in storage battery rooms, (3) In hazardous locations, (4) Underground for direct earth burial, or embedded in poured concrete or aggregate, (5) In lengths over six (6) feet, and (6) in new-construction. Article 71Q -3. Wiring Methods. (a) Aboveground Conductors. Aboveground conductors shall be installed in rigid Metal conduit, in intermediate metal conduit, in cable trays, in cablebus, in other suitable race - ways, or as open runs of metal -clad cable suitable for the use and purpose. Article. 720 -11. Water Meter Conduit. In all new construction metal conduit shall be installed from the water meter location to an outside wall at a point approximately five (5) feet from the front of the building or to a location approved by the electrical inspector. This conduit is for low voltage wiring to a remote reader for the water meter; wiring and reader will be installed by the Department of Public Works. a 1W Chapter 15.08.160 Installation - Inspection - Fees. A. For each nominal fifteen- ampere and twenty- ampere two -wire circuit, including fixtures, sockets or receptacles, the following fees apply: Circuits 1 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Each. additional circuit 15 AMP $ 7.00 11.50 16.00 20.50 25.00 29.50 33.50 37.50 41.50 45.50 48.50 51.50 54.50 57.50 60.50 63.50 66.50 69.50 72.50 75.25 78.00 80.75 83.50 86.25 89.00 $ 2.75 additional over 25 circuits 20 AMP $ 9.00 15.00 21.00 27.00 33.00 38.00 43.00 48.00 53.00 58.00 62.00 66.00 70.00 74.00 78.00 82.00 85.00 88.00 91.00 94.00 97.00 100.00 103.00 106.00 109.00 $ 3.00 additional over 25 circuits B. For each thirty- ampere branch circuit, the inspection fee shall be double the amount of the fifteen - ampere circuit. C. For each forty - ampere branch circuit, the inspection fee shall be double the amount of the twenty - ampere circuit. D. For each fifty - ampere branch circuit, the inspection fee shall be three times the amount of the twenty- ampere circuit. E. A three -wire circuit shall have a multiplier of one and one -half times that listed in subsections A, B, C and D. F. For services including service revisions 60 through 200 ampere, the inspection fee shall be fifteen dollars ($15) plus additional circuits. G. For 2 phase and 3 phase services, including service revisions, the fees shall be: 200 amp 201 to 400 amp 401 to 600 amp 601 to 1000 amp 1001 to 3000 amp H. For feeder circuits, 15 to 100 amp 101 to 200 amp 201 to 400 amp 401 to 600 amp 601 to 1000 amp 1001 to 3000 amp $20.00 40.00 55.00 65.00 75.00 the fees shall be: (2 wi: re (3 wire (4 wi re (3 wire and 4 wire) (3 wire and 4 wire) (3 wire and 4 wire) (3 wire and 4 wire) (3 wire and 4 wire) $10.00 20.00 40.00 55.00 65.00 75.00 a - 7 - W I. The fee for a motor or energy consuming device 3/4 horsepower or over shall be ten dollars ($10) for the first and five dollars ($5) for each additional. Except in single- family dwellings, the fee for a motor one -half horsepower or less, tapped on a branch circuit, shall be one dollar ($1) each. J. Alarm and emergency systems fees are as follows: System Fire alarm system Emergency lighting system Fee $10.00 5.00 + 15 amp circuit rate Intercom & public address system 10.00 per system Master antenna system 10.00 per floor Audio visual (special) 25.00 K. Temporary installations shall pay fees as follows: (,Exhibi:tions, carnivals, outside wiring connected loads) Load Fee Less -than 10 KW $10.00 Connected loads of 10 KW to 50 KW' 25.00 Connected loads of 51 KW to 100 KW 35.00 Connected loads of 101 KW to 200 KW 40.00 Connected loads of 201 KW to 300 KW .50.00 Additfonal connected loads over 300 KW 5.00 for each 100 KW or fraction thereof plan. L. Plan examination fee shall be fifteen dollars ($15) per M. Any rei.nspection or inspection not covered by the fees designated in this section shall be fifteen dollars ($15) per inspector per hour or any part of an hour. SECTION 2: Any person violating the provisions of this chapter shall be punished according to the provis -irons of Chapter 1.08 GENERAL PENALTY. SECTION 3: This Ordinance shall be in full force and effect from and after its passage, approval, and publi,cati ;on Th ;is ordinance may be published in pamphlet form. AYES: 5 Marienthal, Stone, O'Reilly, Hartstein, Oerschefske NAYES: 0 - None ABSENT: 1 - Schwartz PASSED: November 16 1981 APPROVED: November 16 1981 PUBLISHED: November 17 1981 , APPROVED: ZVi page President ATTEST:— `�; :5� ��ri lage Clerk VILLAGE OF BUFFALO GROVE ORDINANCE NO. :�J`5 ADOPTED BY THE PRESIDENT AND BOARD OF TRUSTEES OF THE VILLAGE dd� FF ALO GROVE TH I S DAY OF y &.e . 19 Published in pamphlet form by authority of the President and Board of Trustees of the Village of Buffalo Prove, Coo and Lake Counties, ill'nois, th is —1'7 tt' day of , 19. ORDINANCE NO. 81 55 AN ORDINANCE AMENDING TITLE 15 OF THE VILLAGE OF BUFFALO GROVE MUNICIPAL CODE WHEREAS, the Village of Buffalo Grove is a Home Rule Unit by virtue of the provisions of the Constitution of the State of Illinois of 1970. NOW, THEREFORE, BE IT ORDAINED BY THE VILLAGE PRESIDENT AND BOARD OF TRUSTEES OF THE VILLAGE OF BUFFALO GROVE, COOK AND LAKE COUNTIES, ILLINOIS: SECTION 1: Chapter 15.08 of the Village of Buffalo Grove Municipal'Code is hereby amended to read as follows: Chapter 15:08:010 Adopted by reference. The 1981 National Electrical ,Code. as modified in this chapter is hereby adopted by reference. In the event any of the provisions of the 1981 National Electrical Code are in conflict with any ordinances of the village or with the state law, the most restrictive provision among them shall prevail. ... .... .... I . Chapter 15108.020 Filing. Three copies of the 1981 National Electrical Code shall be kept on file in the office of the village clerk for public use, inspection and examination. .. ... ........ .... .... .... ...... Chapter 15:08.030 Amendments. The 1981 National Electrical Code is hereby amended as follows: Article 110 -23. Identification of Electrical Contractors. The name of the electrical contractor performing the work shall be displayed on the service panel box. .... . .... .... ... _ .. Article 210 -24. Branch- Circuit Requirements -- Summary. The requirements for circuits having two or more outlets, other than the receptacle circuits of Section 220 -3(b) as specifically pro- vided for above, are summarized in Table 210 -24. Detached garages shall be on a separate circuit and shall include the following: (a) A ceiling light controlled by a wall switch. (b) A minimum of one (1) ground fault circuit- interrupter receptacle. Article 210 -52. Dwelling Unit Receptacle Outlets. (a) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sun room, .bedroom, recreation room, foyer, or similar rooms of dwelling units, receptacle outlets shall be installed so that no point along the floor line in any wall space.is more than 6 feet (1.83 m), measured horizontally, from an outlet in that space, including any wall space 2 feet (610 mm) or more in width and the wall space occupied by sliding panels in exterior walls. The wall space afforded by fixed room dividers, such as free - standing bar -type counters, shall be included in the 6 -foot (1.83 -m) measurement. As used in this section a "wall space" shall be considered a wall unbroken along the floor line by doorways, fireplaces, and similar openings. Each wall space 2 or more feet (610 mm or more) wide shall be treated individually and separately from other wall spaces within the room. A wall space shall be permitted to include two or more walls of a room (around corners) where unbroken at the floor line. - 2 - A duplex wall receptacle shall be installed in each hallway. Receptacle outlets shall, insofar as practicable, be spaced equal distances apart. Receptacle outlets -in floors shall not be counted as part of the required number of receptacle outlets unless located close to the wall. The receptacle outlets required by this section shall be in addition to any receptacle that is part of any lighting fixture of applicance, located within cabinets or cupboards, or located over 52 feet (1.68 m) above the floor. Exception: Permanently installed electric baseboard heaters equipped with factory - installed receptacle outlets or outlets provided as a separate assembly by the manufacturer shall be permitted as the required outlet or outlets for the wall space utilized by such permanently installed heaters. Such receptacle outlets shall not be connected to the heater circuits. Article 210 -70. Lighting Outlets Required. Lighting outlets shall be installed where specified in a and b) below. (a) Dwelling Unit(s). At least one wall switch- controlled lighting outlet shall be installed in every habitable room, in bathrooms, hallways, stairways, and attached garages; and at outdoor entrances. Where the preceding are accessible by more than one entry or exit, they shall have a light or lights controlled by a switch at each entry or exit. (A vehicle door in an attached garage is not considered an outdoor entrance.) At least one lighting outlet shall be installed in an attic, underfloor space, utility room and basement. Exception No. 1: In habitable rooms, other than kitchens, one or more receptacles controlled by a wall switch shall be permitted in lieu of lighting outlets. Exception No. 2: In hallways, stairways, and at outdoor entrances remote; central, or automatic control of lighting shall be permitted. Article 225 -10. Wiring on Buildings. The installation of outside wiring on surfaces of buildings shall be permitted for circuits of not over 600 volts, nominal, in rigid metal conduit, in intermediate metal conduit, in rigid nonmetallic conduit as provided in Section 347 -2, in busways as provided in Article 364, or in electrical metallic tubing. Circuits of over 600 volts, nominal, shall be installed as provided for services in Section 230 -202. Circuits for sign and outline lighting shall be installed in accordance. with. Article 600. Article 230 -43. Wiring Methods for 600 Volts Nominal, or Less. Service- entrance conductors shall be installed in accordance w the applicable requirements of this Code covering the type of wiring method used and limited to the following methods: .(1) rigid metal conduit; (2) intermediate metal conduit; (3) elec- trical metallic tubing; (4) service - entrance cables; (5) wireways; (6) busways; (7) auxiliary gutters; (8) rigid nonmetallic conduit; (9) cablebus; or (10) mineral- insulated, metal- sheathed cable. Approved cable tray systems shall be permitted to support cables approved for use as service- entrance conductors. See Arti.cl e.. 318. - 3 - Article 230 -70. General. Means shall be provided to dis- connect all conductors in a building or other structure from the service- entrance conductors. Each service disconnecting means shall be permanently marked to identify it as a service disconnecting means and shall be of the type that is suitable for use as service equipment. Each service disconnecting means shall be suitable for the prevailing conditions. Service equipment installed in hazardous (classified) locations shall comply with the requirements of Articles 500 through 517. A main service disconnect shall be installed for every metered service. Article 230 -79. Rating of Disconnect. The service dis- connecting means shall have a rating not less than the load to be carried, determined in accordance with Article 220. In no case shall the rating be lower than specified in (a), (b), (c), (d), or (e) below. (a) One- Circuit Installation. For installations to supply only limited loads of a single branch circuit, the service disconnecting means shall have a rating of not less than 15 amperes. (b) Two - Circuit Installations. For installations consist- ing of not more than two 2 -wire branch circuits, the service disconnecting means shall have a rating of not less than 30 amperes. (c) One =Fa_ milt' Dwelling. For a one - family dwelling, the service disconnecting means shall have a rating of not less than 100 amperes, 3 -wire under either of the following conditions: (1) where the initial computed load is 10 kW or more, or (2) where the initial installation consists of six or more 2 -wire branch circuits. (d) Commercial and Industrial Buildings. In commercial and industrial buildings, the minimum service shall be two hundred (200) amperes. (e) All Others. For all other installations the service disconnecting means shall have a rating of not less than 60 amperes. Article 230 - 202. Service - Entrance Conductors. Service - entrance conductors to buildings or enclosures shall be installed to conform to the following: (a) Conductor Size. Service conductors shall be not smaller than No. 6 unless in cable. Conductors in cable shall not be smaller than No. 8. (b) Wiring Methods. Service- entrance conductors shall be installed by means of one of the following wiring methods: (1) in rigid metal conduit; (2) in intermediate metal conduit; (3) in rigid nonmetallic conduit where encased in not less than 2 inches (50.8 mm) of concrete; (4) as multiconductor cable identified as service cable; (5) in cablebus; or (6) in busways. Underground service- entrance conductors shall conform to Section 710 -3(b). Cable tray systems shall be permitted to support cables identified as service- entrance conductors. See Article 318. (See Section 310 -6 for shielding of solid dielectric insulated conductors.) Article 250 -91. P�aterial. (d) 'Prohibition of Use of Aluminum Wire. The use of aluminum wire in . ground or below grade for the purpose of grounding is prohibited. -4 Article 300 -1. Scope,. (c) Wiring for all circuits (except lighting circuits) in commercial and industrial buildings shall be 12 AWG rated conductors or larger. Article 310 -5. Minimum Size of Conductors. Whether solid or stranded, conductors shall not be smaller t an No. 14 copper or No. 6 aluminum or copper -clad aluminum. Exception No, 1: For flexible cords as permitted by Section 400 -12. Exception No. 2: Section 410 -23. For fixture wire as permitted by ExcePtion No. 3. For fractional hp by Section 430 -22, motors as permitted Exception No. 4: For cranes and hoists as permitted by Section 610 -14. Exception No. 5: For elevator control and signaling circuits as permitted by Section 620 -12. Exception No. 6: For Class 1, Class 2 and Class 3 circuits as permitted by Sections 725 =16, 725 -37, and 725 -40. Exception No. 7: For fire protective signaling circuits as permitted by Sections 760 -16, 760 -27, and 760 -30. Article 320 -- reference. O en Wirin on Insulators. Not enacted by Article 324 -- Concealed Knob- and =Tube W1 by re erence. . Not enacted Article 328 -4. Uses Permitted. (a) Branch.'Ci:_ Circuits. Use of FCC systems shall be permitted both for general purpose and appliance branch circuits for individual branch circuits. , and (b) Floors. Use of FCC systems shall be permitted on hard, soun , smooth, continuous floor surfaces made of con - Crete, ceramic, or composition flooring, wood, and similar- materials, and shall be used only for reworking obsolete wiring systems in office, commercial and industrial interior facilities or upon written authorization of the building official as to the special circumstances making necessary such permission. (c1' Walls. Use of FCC systems shall be permitted on wall surfaces in surface metal raceways. (d) Damp Locations. Use of FCC systems in damp locations shall be permitted (e), Heated Floors. Materials used in for floors heated excess of 30o C 86oF) shall be identified as suitable for use at these temperatures. Article 333 -6. Use. Except where otherwise specified else- where in this Code, and where not subject to physical damage, Type AC cable shall be permitted for branch circuits and feeders in both exposed and concealed work. Type AC cable shall be permitted in dry locations; for under - plaster extensions as provided in Article 344; and embedded in Plaster finish on brick or other masonry, except in damp or wet locations. It shall be permissible to run or fish this cable in the air voids of masonry block or tile walls; where such walls are exposed or subject to excessive moisture or dampness or are below grade line, Type ACL cable shall be used. contain lead- covered conductors (Type ACL) if used This to the weather or to continuous moisture; for underground runs in raceways and embedded in masonry, concrete, or fill in buildings in course of construction; or where exposed to oil, or other conditions having a deteriorating effect on the insulation. - 5 - Type AC cable shall not be used where prohibited elsewhere in this Code, including (1) in theaters and similar locations, except as provided in Article 518, Places of Assembly; (2) in motion picture studios; (3) in any hazardous (classified) location; (4) where exposed to corrosive fumes or vapors; (5) on cranes or hoists, except as provided in Section 610 -11, Exception No. 3; (6) in storage battery rooms; (7) in hoistways or on elevators, except as provided in Section 620 -21; or (8) in commercial garages where prohibited in Article 511. Type AC cable shall not be used in new construction in lengths of greater than six (6) feet. Exception: See Section 501 -4(b), Exception. Type ACL cable shall not be used for direct burial in the earth. Article 334 -4. Uses'Not Permitted. Type MC cable shall not be used where exposed to destructive corrosive conditions, such as direct burial in the earth, in concrete, or where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids. Type MC cable shall not be used in new construction in lengths of greater than six (6) feet. Exception: Where the metallic sheath is suitable for the conditions or is protected by material suitable for the conditions. Article 336 -3. 'Uses Permitted or Not Permitted. Not enacted by reference. Article 349 -3.' Uses Permitted. Flexible metallic tubing Shall be permitted to be used: (1) In dry locations, (2) In accessible locations when protected from physical damage or concealed, (3) For 1000 volts maximum, (4) In branch circuits, (5) In final connections to lighting fixtures and equipment, and (6) For remodeling work and in confined spaces. Article 349 -4. Uses Not Permitted. Flexible metallic tubing shali not be used: (1) In hoistways, (2) In storage battery rooms, (3) In hazardous locations, (4) Underground for direct earth burial, or embedded in poured concrete or aggregate, (5) In lengths over six (6) feet, and (6) In new construction. Article 710 -3. Wiring Methods. (a) Aboveground Conductors. Aboveground conductors shall be installed in ri:gid metal conduit, in intermediate metal conduit, in cable trays, in cablebus, in other suitable race- ways, or as open runs of metal - clad -cable suitable for the use and purpose. Article 720 -11. Water Meter Conduit. In all new construction metal conduit shall be installed from the water meter location to an outside wall at a point approximately five (5) feet from the front of the building or to a location approved by the electrical inspector. This conduit is for low voltage wiring to a remote reader for the water meter; wiring and reader will be installed by the Department of Public Works. - 6 - Chapter 15.08.160 Installation - Inspection - Fees. A. For each nominal fifteen - ampere and twenty- ampere two -wire circuit, including fixtures, sockets or receptacles, the following fees apply: Circuits 15 AMP 20 AMP 1 $ 7.00 $ 9.00 2 11.50 15.00 3 16.00 21.00 4 20.50 27.00 5 25.00 33.00 6 29.50 38.00 7 33.50 43.00 8 37.50 48.00 9 41.50 53.00 10 45.50 58.00 11 48.50 62.00 12 51.50 66.00 13 54.50 70.00 14 57.50 74.00 15 60.50 78.00 16 63.50 82.00 17 66.50 85.00 18 69.50 88.00 .19 72.50 91.00 20 75.25 94.00 21 78.00 97.00 22 80.75 100.00 23 83.50 103.00 24 86.25 106.00 25 89.00 109.00 Each. additional $ 2.75 additional $ 3.00 additional circuit over 25 circuits over 25 circuits B. For each thirty- ampere branch circuit, the inspection fee shall be double the amount of the fifteen - ampere circuit. C. For each forty- ampere branch circuit, the inspection fee shall be double the amount of the twenty- ampere circuit. D. For each fifty- ampere branch circuit, the inspection fee shall be three times the amount of the twenty- ampere circuit. E. A three -wire circuit shall have a multiplier of one and one -half times that listed in subsections A, B, C and D. F. For services including service revisions 60 through 200 ampere, the inspection fee shall be fifteen dollars ($15) plus additional circuits. G. For 2 phase and 3 phase services, including service revisions, the fees shall be: 200 amp 201 to 400 amp 401 to 600 amp 601 to 1000 amp 1001 to 3000 amp H. For feeder circuits, 15 to 100 amp 101 to 200 amp 201 to 400 amp 401 to 600 amp 601 to 1000 amp 1001 to 3000 amp $20.00 40.00 55.00 65.00 75.00 the fees shall be: (2 wire ) (3 wire $10.00 (4 wire (3 wire and 4 wire) 20.00 (3 wire and 4 wire) 40.00 (3 wire and 4 wire) 55.00 (3 wire and 4 wire) 65.00 (3 wire and 4 wire) 75.00 - 7 - I. The fee for a motor or energy consuming device 3/4 horsepower or over shall be ten dollars ($10) for the first and five dollars ($5) for each additional. Except in single- family dwellings, the fee for a motor one -half horsepower or less, tapped on a branch circuit, shall be one dollar ($1) each. J. Alarm and emergency systems fees are as follows: System Fee Fire alarm system $10.00 Emergency lighting system 5.00 + 15 amp Intercom &public address circuit rate system 10.00 per system Master antenna system 10.00 per floor Audio visual (special) 25.00 K. Temporary installations shall pay fees as follows: (Exhibi:tions; carnivals, outside wiring connected loads) Load: Fee Less.than 10 KW $10.00 Connected loads of 10 KW to 50 KW 25.00 Connected loads of 51 KW to 100 KW 35.00 Connected loads of 101 KW to 200 KW 40.00 Connected loads of 201 KW to 300 KW 50.00 Additional connected loads over 300 KW 5.00 for each 100 KW or fraction thereof plan. L. Plan examination fee shall be fifteen dollars ($15) per M. Any retnspection or inspection not covered by the fees designated in th.i:s section shall be fifteen dollars ($15) per inspector per hour or any part of an hour. SECTION 2: Any person violating the provisions of this chapter shall be punished according to the provisions of Chapter`1.08 GENERAL PENALTY. SECTION 3: ThA s Ordinance shall be in full force and effect from and after its passage, approval, and publi.cati_on,This ordinance may be published in pamphlet form. AYES: 5 - Marienthal, Stone.,.0'Reitly, Hartstein, Gerschefske NAPES: 0 - None ABSENT: 1 - Schwartz PASSED: November 16 1981 APPROVED: November 16 1981 PUBLISHED: November 17 1981 r APPROVED: i lage President ATTEST:_tm'} T�'iY 1 aClerk